Testing intervals

Below is a guide only. For full details refer to the Australian Standard AS/NZS 3760 (current edition AS/NZS 3760:2022). This table matches the interval chart Test Tag n Repair has published on this site.

Guide to intervals between inspection and tests — AS/NZS 3760. Not a substitute for the Standard.
(a) Type of environment and/or equipment Interval between inspection and tests
Class of equipment Residual Current Devices (RCDs) (h) Cord sets and power boards
(b) Class I
(protectively earthed)
(c) Class II
(double insulated)
Push-button test — by user Operating time and push-button test
(d) Portable (e) Fixed (f) Portable (g) Fixed
1 Factories, workshops, places of work or repair, manufacturing, assembly, maintenance or fabrication 6 months 12 months Daily, or before every use, whichever is the longer 6 months 12 months 12 months 6 months
2 Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment 12 months 12 months 3 months 6 months 12 months 12 months 12 months
3 Environment where the equipment or supply cord is NOT subject to flexing in normal use and is NOT open to abuse and is NOT in a hostile environment 5 years 5 years 3 months 6 months 2 years 2 years 5 years
4 Residential type areas of: hotels, residential institutions, motels, boarding houses, halls, hostels, accommodation houses, and the like 2 years 2 years 6 months 6 months 2 years 2 years 2 years
NB. Construction site: 3 months
5 Equipment used for commercial cleaning 6 months 12 months 3 months N/A 12 months N/A 12 months
6 Hire equipment Inspection: Prior to hire Including push-button test by hirer prior to hire N/A N/A Prior to hire
Test and tag: 3 months N/A 3 months 12 months 3 months
7 Repaired, serviced and second-hand equipment After repair or service which could affect electrical safety, or on reintroduction to service.

This is a guide only. Confirm the correct interval for your workplace against the current Standard and your risk assessment.

Need testing in Launceston or North Tasmania?

Ph: 0418 518 409

Original interval chart

The chart Test Tag n Repair has used on this site is also available as an image:

AS/NZS 3760 testing interval guide chart used by Test Tag n Repair

Download the original interval chart (GIF)